SCHALTVERSTÄRKER 521
ELECTRONIC ACCESSORY | DISPLAY AND CONTROL DEVICES
The switching amplifier is preferably used for binary signal transmission of water meters.
The switching amplifier is frequently used as pulse extension relay for fast running processes. It can be used as contact protection relay or non-bounce relay when being triggered by a volt-free contact transmitter (reed switch).
If required, the two binary inputs can be added to one output-channel (via turn switch).
- Snap-bar case version
- Triggered on choice by contact transmitter, infrared transmitter and two-wire primer (NAMUR)
- Each output is a opto-coupler with one no-contact
- Two volt-free outputs, solid state relay, no-contact
- Galvanically isolated measurement and supply circuits
- Adjustable impulse period
- 3 different pulse length, adjustable via turn switch
- Pulse-addition adjustable via turn switch
- Power supply 20 ... 250 V AC/DC
-
Technical Data
Supply voltage Wide range power supply 20 ... 250 V AC/DC, 100 mA ... 20 mA Display LED display for output pulses Storage temperature °C -40 ... +70 Operating temperature °C 0 ... +55 Output - type Solid stay relay (SSR), output volt-free Output - load Max. 230 V / 100 mA ~ Min. input pulse duration 6 ms Max. input pulse duration Infinite Outputs Can be switched over via turn switch; S1 = Channel 1, S2 = Channel 2 Inputs Initiator 571 / 572; Reed switch 570, IR transmitter 571, PV14 Housing - type Snap-on housing Housing - fixing Mounting rail to EN 50022 (35 x 7.5) Protection class - housing IP 20 Protection class - terminal IP 10 Weight g 200 Separate working outputs (SX = Channel 1 or Channel 2)
SX = 0 | OutputX = InputX --> direct transmission / permanent contact
SX = 2 | OutputX = InputX with 0.1 sec output pulse __|¯|_________
SX = 3 | OutputX = InputX with 0.3 sec output pulse __|¯¯¯|_______
SX = 4 | OutputX = InputX with 2 sec output pulse __|¯¯¯¯¯¯¯|___
Input-Addition (Channel 1 + 2) --> OutputX (max. up to 100 pulses per channel in memory)
SX = 9 | OutputX = E1 + E2 with 0.1 sec output pulse __|¯|_________
SX = A | OutputX = E1 + E2 with 0.3 sec output pulse __|¯¯¯|_______
SX = B | OutputX = E1 + E2 with 2 sec output pulse __|¯¯¯¯¯¯¯|___ -
Technical Data Inputs
Initiator 572, 573 8 mA (short-circuit-current), 1.6 mA (switching point) Reed switch 570 8 mA (short-circuit-current), 1.6 mA (switching point) IR transmitter 571 5 mA (short-circuit-current), 1.0 mA adjustable by front trimmer (switching point) PV14 5 mA (short-circuit-current), 1.0 mA (switching point) - Dimensions
-
Order References
Remark Switching Amplifier (Snap Bar) (SSR) 20 ... 250 V AC/DC Article number 521 000 16 - Operation turn switch | Connections
- Pin Assignment
- Connection of sensors
- Connection of sensors / meters