PROMAG

ELECTROMAGNETIC FLOW SENSOR

Application

The electromagnetic flowmeter PROMAG designed for measuring heating water or any other type of conductive liquids used in air conditioning systems. It is characterized by high measuring accuracy and extended measuring range. Free of any moving parts, PROMAG offers a wide range of original technical solutions to suit various applications, such as glycol water measurement at -40°C to overheated water at +130°C.
Combined with a CALEC ST III or SCYLAR INT 8 calculator, PROMAG is, all year round, the ideal hydraulic part of energy measurement.

Features

  • All liquids measurement with a conductivity > 5 µS/cm
  • No mechanical moving part
  • Process temperature range: -40°C to +130°C
  • Very low pressure drop
  • Pulse output and analogue output 4 ... 20 mA
  • Bluetooth configuration
  • General
    ApplicationHeating / cooling (without commercial transaction)
    Measuring accuracy%+/- 0.5
    Ambient temperature°C-20 ... +60
    Power supply100 to 240 V AC ; ± 10% | 50 to 60 Hz ; ±5 Hz
    Mounting positionAny position
    Degree of protectionIP67
    Pulse outputAdjustable pulse width: 0.05 ... 2,000 ms
    Current output4 ... 20 mA
    Status outputError message or flow direction recognition
    Minimal conductivityμS/cm5
    Power consumption200 mA max
    Galvanic isolationAll circuits for inputs, outputs and power supply are galvanically insulated from each other
    EMC compatibilityAccording to EN61326 and NAMUR NE21
    Drinking water certificationACS for PROMAG W 10
    Parameters adjustmentOn display or Bluetooth with the SmartBlue application for Android
  • Technical data flow sensor
    Nominal diameterDNmm253240506580100125150200250300350400500
    Maximal flowrateqsm³/h183042661201802824506001,1001,7002,4003,3004,2006,600
    Minimal flowrateqim³/h0.540.91.52.13.65.48.713.220355580110140220
    Pulse weightl/pulse11111010101001001001001001001,0001,000
  • Cold application (PROMAG W 10) ACS certified
    Nominal diameterDNmm253240506580100125150200250300350400500
    Polyurethane coating - T. -20°C to +50°C - compact versionPNbar404040401616161616101010101010
  • Ambiant application (PROMAG P 10)
    Nominal diameterDNmm253240506580100125150200250300350400500
    Polyurethane coating - T. -20°C to +110°C - compact versionPNbar161616161616-1616101010---
  • Hot application (PROMAG P 10)
    Nominal diameterDNmm253240506580100125150200250300350400500
    Polyurethane coating - T. -40°C to +130°C - compact versionPNbar161616161616161616101010101010
  • PROMAG W 10 : Dimensions, weight and connections
    Nominal diameterDNmm253240506580100125150200250300350400500
    Lmm200200200200200200250250300350450500550600650
    Emm120120120120180180180260260324400460490542648
    Bmm178178178178178178178178178178178178178178178
    Amm139139139139139139139139139139139139139139139
    Cmm258258258258283283283323323348373398457483490
    Dmm84848484109109109150150180205230245271324
    WeightKg101112131315182531528195106121156
  • PROMAG P 10 : Dimensions, weight and connections
    Nominal diameterDNmm253240506580100125150200250300350400500
    Lmm200200200200200200250250300350450500550600650
    Emm120120120120180180180260260324400460564616717
    Bmm136136136136136136136136136136136136136136136
    Amm148148148148148148148148148148148148148148148
    Cmm197197197197222222222262262287312337396422472
    Dmm84848484109109109150113180205230282308359
    WeightKg88.710.111.312.714.716.722.226.245.765.770.7105.7120.7156.7