SHARKY FS 473
ULTRASONIC FLOW SENSOR
Application
SHARKY FS ultrasonic flow sensor is designed for flow measuring in local and district heating and heating/cooling systems. The ultrasonic technology used is based on the static measurement of the transit time and offers many benefits : no moving parts (prevents wear and tear of the metering components), low pressure loss, large metering dynamics and low start flowrate, resistance to suspended particles...
Features
- Approval with dynamic range up to 1:250 (qi:qp) MID in class 2 (depending on meter size), standard 1:100
- Complete range from DN 15 qp 0.6 m³/h up to DN 100 qp 100 m³/h
- Available in threaded or flanged version
- Heat-transfer fluid: glycol-free water
- External power supply as standard or battery-driven as an alternative
- Low power consumption ensuring optimum battery lifetime (up to 12 years)
- Applicable for calculators with pulse input
- Temperature range 5°C to 90°C / 5°C to 150°C
-
General
Application Heating or bifunctional (heating/cooling) | Heat-transfer fluid: glycol-free water Approval MID (DE-07-MI004-PTB022) Ambient class EN 1434 class C / MID class E2 + M2 Ambient temperature °C +5 ... +55 Power supply External power supply: 3.0 ... 5.5 VDC | Battery suply: 3.0 VDC (up to 12 years lifetime) Mounting position Any position Protection class Heating: IP 54; heating/cooling: IP 65 Interfaces Open Collector pulse output1 - output for testing and communication2 Volume pulse value3 10 ml ... 5,000 l/pulse (depending on sensor sizes and supply) Pulse cable length 2.4 m (4.9 or 9.9 m optional) Material of the flow sensor body Brass (qp 0.6 ... 10 m³/h), grey cast iron (qp 15 ... 100 m³/h) 1 The pulse output can be chosen without galvanic isolation (standard) or with galvanic isolation (only with battery supply). The flow sensor has by default a 4-wires pulse cable.
2 The output for testing is a combined pulse output. The flow sensor can either emit a high resolution test pulse (standard) or communicate via the same output.
3 The pulse duration is between 1 and 250 ms depending on the pulse value and the nominal flow rate qp.
Standard pulse values: 1, 10, 100 l/pulse (other pulse values available on request). -
-
Temperature range
Temperature range heating - battery supply °C +5 ...+90 / +5 ... +1051 Temperature range heating - external supply °C +5 ... +130 / +150 Temperature range heating/cooling - battery supply °C +5 ... +90 / +5 ... +1051 1 Only in rising or falling pipes or tilted horizontal installation -
Technical data
Nominal flow rate qp m3/h 0.6 1.5 1.5 2.5 6 6 10 15 25 40 60 100 Nominal diameter DN mm 15 15 20 20 25 32 40 50 65 80 100 100 Overall length L mm 110 110 130 130 260 260 300 270 300 300 360 360 Starting flow rate l/h 1 2.5 2.5 4 10 10 20 40 50 80 120 120 Minimum flow rate (DR 1:250) qi l/h - 6 6 10 24 24 401 601 1001 1601 2401 4001 Minimum flow rate (DR 1:100) qi l/h 6 15 15 25 60 60 100 150 250 400 600/1,2002 1,000/1,2002 Minimum flow rate (up side down installation) qi l/h 6 6 6 10 24 24 100 150 250 400 1,200 1,200 Maximum flow rate qs m³/h 1.2 3 3 5 12 12 20 30 50 80 120 120 Overload flow rate m³/h 2.5 4.6 4.6 6.7 18.4 18.4 24 36 60 90 132 132 Pressure loss at qp Δp mbar 95 120 75 100 128 165 140 140 75 80 75 210 Temp. range heating °C 5 ... 130 5 ... 130 5 ... 130 5 ... 130 5 ... 150 5 ... 150 5 ... 150 5 ... 150 5 ... 150 5 ... 150 5 ... 150 5 ... 150 Kvs value (Δp=Q2/Kvs2) 1.95 4.33 5.48 7.91 16.77 14.77 26.73 40.09 91.29 141.42 219.09 218.22 1 Valid for horizontal installation only
2 Up side down installation -
Dimensions thread version
Nominal flow rate qp m3/h 0.6 1.5 1.5 2.5 6 6 10 15 25 40 60 100 Nominal diameter DN mm 15 15 20 20 25 32 40 50 65 80 100 100 Overall length L mm 110 110 130 130 260 260 300 270 300 300 360 360 Overall length with coupling L2 mm 190 190 230 230 380 380 440 - - - - - Height H mm 14.5 14.5 18 18 23 23 33 - - - - - Height H1 mm 54.5 54.5 56.5 56.5 61 61 66.5 - - - - - Length of electronic L1 mm 90 90 90 90 90 90 90 - - - - - Width of electronic B mm 65.5 65.5 65.5 65.5 65.5 65.5 65.5 - - - - - Connection thread on meter Inch G¾B G¾B G1B G1B G1¼B G1½ B G2B - - - - - Connection thread of coupling Inch R½ R½ R¾ R¾ R1 R1¼ R1½ - - - - - Operating pressure PN bar 16/25 16/25 16/25 16/25 16/25 16/25 16/25 - - - - - Weight kg 0.6 0.6 0.61 0.61 1.35 1.35 2.6 - - - - - -
Dimensions flange version
Nominal flow rate qp m3/h 0.6 1.5 1.5 2.5 6 6 10 15 25 40 60 100 Nominal diameter DN mm 15 15 20 20 25 32 40 50 65 80 100 100 Overall length L mm 110 110 130 130 260 260 300 270 300 300 360 360 Height H mm - - - - 50 62.5 69 73.5 85 92.5 108 108 Height H1 mm - - - - 61 61 66.5 71.5 79 86.5 96.5 95.5 Length of electronic L1 mm - - - - 90 90 90 90 90 90 90 90 Width of electronic B mm - - - - 65.5 65.5 65.5 65.5 65.5 65.5 65.5 65.5 Flange dimension F mm - - - - 100 125 138 147 170 185 216 216 Flange diameter D mm - - - - 114 139 148 163 184 200 235 235 Hole circle diameter K mm - - - - 85 100 110 125 145 160 190 190 Screwhole diameter D1 mm - - - - 14 18 18 18 18 19 22 22 Operating pressure PN bar - - - - 16/25 16/25 16/25 16/25 16/25 16/25 25 25 Number of screwholes pcs - - - - 4 4 4 4 8 8 8 8 Weight brass body1 kg - - - - 3.35 4.65 6.6 7.45 9.45 11.1 16.9 16.9 Weight grey cast iron body1 kg - - - - - - - 6.31 8.08 10.01 15.76 15.75 1 Meter with battery and 2.4 m cable length of the pulse cable -
Pressure loss graph / typical error graph