SCYLAR INT 8

SCYLAR INT 8

ENERGY CALCULATOR

Application

SCYLAR INT 8 is a high-precision calculator designed to meet European standards. It measures heating, cooling energy and can be used in combined mode too. SCYLAR INT 8 enables the utility to monitor and optimize its metering remotely; it can be directly connected to a Centralized Technical Management unit, to provide large quantities of instant or saved parameters.

Features

  • MID approved
  • Heating or bifunctional (heating/cooling) version
  • Heat-transfer fluid: glycol-free water
  • Low power consumption for enhanced battery lifetime (up to 16 years in standard use)
  • Suitable for 2 and 4 wires temperature sensor connection
  • Integrated radio option
  • Modular version, M-Bus, RS232, RS485, Analog outputs 4-20mA, pulse outputs and pulse inputs
  • General
    ApplicationHeating or bifunctional (heating/cooling) | Heat-transfer fluid: glycol-free water
    ApprovalMID (DE-10-MI004-PTB004)
    Protection classIP 54
    Battery supply3.6 VDC D-cell up to 16 years lifetime*
    Mains supply24 VAC; 230 VAC / ≤ 0.15 W
    Volume pulse input frequencyMax. 200 Hz; pulse duration > 3 ms
    Pulse valuel/pulse1, 10, 100 and 1,0001
    Temperature sensor typePt 500 with 2- or 4- wire leads; Ø 5.2mm
    Cable length of temperature sensorPt 500: 2/5/10m
    Calculation cycles2
    1 Depending on size of flow sensor

    *Standard conditions of use and temperature. Theoretical life, with no guarantee.
  • Basic features
    Ambient class (MID)Class E2 + M2
    Ambient temperature°C0 ... +55
    Ambient storage temperature°C-25 ... +60 (>35 °C max. 4 weeks)
    Communication3 communication interfaces (e. g. M-Bus + M-Bus + Int. Radio; 2 primary addresses, 1 secondary address)
    Integrated RadioOptional
    Interfaces standardOptical ZVEI interface
    Interfaces optional2 slots for modules with M-Bus, L-Bus, RS232, RS485, pulse output, pulse input, combined pulse in-/output or analogue output
    Temperatures range°C0 ... +180
  • Integrated Radio
    Frequency band868 or 434 MHz
    Type of radio telegramOpen Metering Standard (OMS) profile A & B
    Transmission data updatingOnline - no time delay between value measurement and data transmission
    Data transmissionUnidirectional T1 mode
    Sending interval12s (up to 16 years lifetime*) depending on length of telegram (duty cycle)
    *Standard conditions of use and temperature. Theoretical life, with no guarantee.
  • Display
    Display indicationLCD, 8-digit
    UnitsMWh - kWh - GJ - Gcal - MBtu - gal - GPM - °C - °F - m³ - m³/h
    Total values99,999,999 - 9,999,999.9 - 999,999.99 - 99,999.999
    Displayed valuesEnergy - Volume - Flow rate - Power -Temperatures
  • Interfaces
    OpticalZVEI interface, for communication and testing, M-Bus protocol, 2,400 bauds
    M-BusConfigurable telegram according to EN13757-3, data reading and parametrization are via 2 wires with polarity reversal protection, auto baud detect (300 and 2,400 bauds), 2 M-Bus with 2 primary addresses
    L-BusAdapter for external radio module, configurable telegram according to EN13757-3, data reading and parametrization are via 2 wires with polarity reversal protection
    RS232Serial interface for communication with external devices, a special data cable is required, M-Bus protocol, 300 and 2,400 bauds
    RS485Serial interface for communication with external devices, power supply with 12 V ± 5 V, M-Bus protocol, 2,400 bauds
    Pulse outputModule with 2 Open Collector pulse outputs (potential-free), output 1: 4 Hz (pulse width 125 ms), pulse or static conditions (e.g. errors), output 2: 200 Hz (pulse width ≥ 5 ms), ratio: pulse duration / pulse break ~ 1:1, configurable via IZAR@MOBILE 2 software
    Pulse inputModule with 2 pulse inputs, max. 20 Hz, configurable via IZAR@MOBILE 2 software, data can be transferred remotely
    Combined pulse in-/outputModule with 2 pulse inputs and 1 pulse output, configurable via IZAR@MOBILE 2 software, needed for leak detection
    Analogue outputModule for 4 ... 20 mA with 2 programmable passive outputs, programmable value in case of error
  • Temperature input
    Measuring cycleTsWith mains unit: 2s | with D-cell battery: 4s
    Starting temperature differenceΔΘK0.125
    Min. temperature differenceΔΘminK3
    Max. temperature differenceΔΘmaxK175
    Absolute temperature measuring rangeΘ°C-20 ... +190
  • Dimensions
    Overall lengthLmm150
    Width of calculatorBmm100
    HeightHmm54

You are currently using an outdated Internet browser, which is no longer supported for technical reasons. To use the Diehl website right, please use a modern browser in the latest version, such as Edge, Chrome, Firefox or Safari.

Consent

We would like to use Google Analytics to optimise the design of our website. Through this, Google collects data which is aggregated and made available to us as a statistical overview. By clicking "Agree", you consent to tracking by Google Analytics. This consent is voluntary and can be revoked at any time. If you click "Decline", no tracking will take place. For more information, please see our privacy policy.