SHARKY FS 473

FLOW SENSOR- ULTRASONIC

Application

The ultrasonic flow sensor can be used for flow measuring in local and district heating / cooling systems.

Features

  • Dynamic range (DR) of up to 1:250 (qi:qp) in class 2 (depends on meter size), standard 1:100
  • Extreme low power consumption --> longer battery lifetime
  • Approved according EN 1434 and MID in class 2 and 3 and PTB K 7.2 (cooling)
  • High long term stability
  • Applicable for different calculators with impulse input
  • Continuous time-correct pulses - no pulse packages
  • Free selectable impulse values
  • The temperature range depending on the applicaton up to 5 ... 150 °C
  • Battery or external power supply
  • Specific housing for falling and rising pipes
  • General
    ApplicationHeating - cooling
    ApprovalMID (DE-07-MI004-PTB022) and PTB K 7.2 for cooling (22.76/10.01)
    Ambient classEN 1434 class C / MID class E2 + M2
    Ambient temperature°C5 ... 55 (<35 °C have a positive lifetime effect)
    Battery supply3.0 VDC battery - up to 12 years lifetime
    External supply3.0 ... 5.5 VDC
    Mounting positionAny position
    Protection classHeating: IP 54; heating potted: IP 65; cooling: IP 65
    InterfacesOpen Collector pulse output1 - output for testing and communication2
    Volume pulse value310 ml ... 5000 l/pulse (depending on sensor sizes and supply)
    Cable length of impulse cable2.4 m (4.9 or 9.9 m optional)
    Material of the flow sensor bodyBrass (qp 0.6 ... 100 m³/h), spheroidal cast iron (qp 15 ... 100 m³/h)
    1 The pulse output can be choosen without galvanic isolation (standard) or with galvanic isolation (only with battery supply). The flow sensor has by default a 4-wire impulse cable.
    2 The flow sensor can either emit a high resolution test pulse (standard) or communicate via the same output. By using an adapter the flow sensor can be read via the HYDRO-SET software.
    3 The pulse duration is between 1 and 250 ms. It depends on the pulse value and on the nominal flow rate qp.
    Standard pulse values: 1, 2.5, 10, 25, 100, 250 l/pulse
  • Reach

    Information pursuant to Article 33 (1) of Regulation (EC) No 1907/2006 of the European Parliament and of the Council of 18 December 2006:
    This product series contains articles with the following substances in a concentration of more than 0.1% weight by weight (w/w):
    - Lead

  • Temperature range
    Temperature range heating - battery supplied°C5 ... 90 / 5 ... 1051
    Temperature range heating - external supplied°C5 ... 105 / 130 / 150 (depends on meter size and material)
    Temperature range cooling - battery supplied / external supplied°C5 ... 50 / 5 ... 90
    1 Only in rising or falling pipes or tilted horizontal installation
  • Technical data
    Nominal flow rateqpm3/h0.60.60.61.51.51.52.52.53.53.53.53.53.5666666101015254060100
    Nominal diameterDNmm1520 20 15 20 20 20 20 25 25 2532 32 25 25 2532 324040 40 50 6580100100
    Overall lengthLmm 110 130 190 110 130 190 130 190135150 260150 260135150 260150 260150200 300 270 300300360360
    Starting flow ratel/h1112.52.52.54410101010101010101010102020405080120120
    Minimum flow rate (DR 1:250)qil/h 6 6 6 6 6 6 1010-----24242424 24-4014016011001160124014001
    Minimum flow rate (DR 1:100)qil/h66615151525253535353535606060606060100100150250400600/120021000/12002
    Minimum flow rate (up side down installation)qil/h66666610103535353535242424242410010015025040012001200
    Maximum flow rateqsm³/h 1.2 1.2 1.2 3 3 3 5 5 7 7 7 7 7 12 12 12 12 12122020305080120120
    Overload flow ratem³/h 2.5 2.5 2.5 4.6 4.6 4.6 6.7 6.7 18.4 18.4 18.4 18.4 18.4 18.4 18.4 18.4 18.4 18.418.424 24 36 6090132132
    Pressure loss at qpΔpmbar95858512075751001004444444444128128128128128190140140140758075210
    Temp. range heating - brass body°C5 ... 1305 ... 1305 ... 1305 ... 1305 ... 1305 ... 1305 ... 1305 ... 1305 ... 1505 ... 1505 ... 1505 ... 1505 ... 1505 ... 1505 ... 1505 ... 1505 ... 1505 ... 1505 ... 1505 ... 1505 ... 1505 ... 1505 ... 1505 ... 1505 ... 1505 ... 150
    Temp. range heating - spheroidal cast iron body / brass PN 40°C---------------------5 ... 1055 ... 1055 ... 1055 ... 1055 ... 105
    kv value (qp² (m³/h) = kv² x Δp (bar))1.952.062.064.335.485.487.917.9116.6916.6916.6916.6916.6916.7716.7716.7716.7716.7713.7626.7326.7340.0991.29141.42219.09218.22
    1 Valid for horizontal installation only
    2 Up side down installation
  • Dimensions thread version
    Nominal flow rateqpm3/h0.60.60.61.51.51.52.52.53.53.53.53.53.5666666101015254060100
    Nominal diameterDNmm1520 20 15 20 20 20 20 25 25 2532 32 25 25 2532 324040 40 50 6580100100
    Overall lengthLmm 110 130 190 110 130 190 130 190135150 260150 260135150 260150 260150200 300 270 300300360360
    Overall length with couplingL2mm190230-190230-230-255270380270380255270380270380-340440-----
    HeightHmm 14.5181814.51818181823232323232323232323333333-----
    HeightH1mm 54.556.556.554.556.556.556.556.5616161616161616161616166.566.5-----
    Length of electronicL1mm 909090909090909090909090909090909090909090-----
    Width of electronicBmm65.565.565.565.565.565.565.565.565.565.565.565.565.565.565.565.565.565.565.565.565.5-----
    Connection thread on meterInchG¾BG1BG1BG¾BG1BG1BG1BG1BG1¼BG1¼BG1¼BG1½BG1½ BG1¼BG1¼BG1¼BG1½BG1½ BG2BG2BG2B-----
    Connection thread of couplingInchR1R1R1R1¼R1¼R1R1R1R1¼R1¼R1½R1½R1½-----
    Operating pressurePNbar16/2516/2516/2516/2516/2516/2516/2516/2516/2516/2516/2516/2516/2516/2516/2516/2516/2516/2516/2516/2516/25-----
    Weightkg0.60.610.630.60.610.630.610.630.880.931.351.081.350.880.931.351.081.351.522.42.6-----
  • Dimensions flange version
    Nominal flow rateqpm3/h0.60.60.61.51.51.52.52.53.53.53.53.53.5666666101015254060100
    Nominal diameterDNmm1520 20 15 20 20 20 20 25 25 2532 32 25 25 2532 324040 40 50 6580100100
    Overall lengthLmm 110 130 190 110 130 190 130 190135150 260150 260135150 260150 260150200 300 270 300300360360
    HeightHmm--47.5--47.5-47.5--50-62.5--50-62.5--6973.58592.5108108
    HeightH1mm--56.5--56.5-56.5--61-61--61-61--66.571.57986.596.595.5
    Length of electronicL1mm--90--90-90--90-90--90-90--909090909090
    Width of electronicBmm--65.5--65.5-65.5--65.5-65.5--65.5-65.5--65.565.565.565.565.565.5
    Flange dimensionFmm--95--95-95--100-125--100-125--138147170185216216
    Flange diameterDmm--105--105-105--114-139--114-139--148163184200235235
    Hole circle diameterKmm--75--75-75--85-100--85-100--1101251451601801 / 1901801 / 190
    Screwhole diameterD1mm--14--14-14--14-18--14-18--18191919191 / 22191 / 22
    Operating pressurePNbar--16/25--16/25/403-16/25/403--16/25/403-16/25/403--16/25/403-16/25/403--16/25/40316/25/40316/2516/25/40316/2516/25
    Number of screwholespcs--4--4-4--4-4--4-4--448888
    Weight brass body2kg--2.7--2.7-2.7--3.35-4.65--3.35-4.65--6.67.459.4511.116.916.9
    Weight spheroidal cast iron body2kg---------------------6.318.0810.0115.7615.75
    1 Values for PN 16 housing
    2 Meter with battery and 2.4 m cable length of the pulse cable
    3 Only up to 105 °C
  • Pressure loss graph / typical error graph