Application
IZAR PORT PULSE offers the possibility to connect resource meters with pulse output to an M-Bus network (transformation of pulses to M-Bus protocol). It is suitable for all meter types with a pulse transmitter, open collector or current loop (S0) output.
Features
- Two independent pulse counters
- Configuration via M-Bus interface or optical ZVEI interface using HYDRO-PORT software
- Physical unit and medium programmable for each input
- Pulse divisor programmable for each input
- Power supply via M-Bus, Backup battery to ensure pulse counting if M-Bus fails
- External power suppy input for connecting meters with current loop (S0) output
-
Principle of operation
IZAR PORT PULSE consists of an electronic unit that collects meter pulses which are converted into physical units. The data is transmitted via M-Bus protocol to a data concentrator (M-Bus Master IZAR CENTER).
-
General
Housing Light-grey rail mount housing with fuse profile Cable length Max. 1.5 m for connecting pulse transmitter / open collector Interfaces M-Bus output; Input for external power supply; at a time 2 inputs for pulse (voltage-free) and current loop (S0) contacts; optical ZVEI interface Configuration Via ZVEI or M-Bus and HYDRO-PORT software (free of charge) -
Technical data
Power supply Via M-Bus or Lithium battery 3.6 V Power supply (S0) V 24 Pulse frequency Hz Max. 50 Pulse width ms Min. 7.5 Weight g 150 Protection class IP 20 -
Ambient conditions
Humidity max. % 70 Temperature range °C 0 ... 60 -
Dimensions
Length L mm 71 Width B mm 86 Width 1 B1 mm 49 Width 2 B2 mm 32 Height H mm 60 Height 1 H1 mm 49 Height 2 H2 mm 32