HYDRUS 2.0 GWZ

HYDRUS 2.0 GWZ

ULTRASONIC METER

HYDRUS 2.0 BULK is a static ultrasonic bulk water meter designed for all applications of cold water supply enabling accurate measuring with long-term stability under difficult conditions (no measurement of air and insensitive to sedimentation). Developed within the framework of the MID, it complies with the European regulations and holds sanitary conformity certificates (KTW/W270, ACS, WRAS and others). The integrated communication function supports meter data provision via mobile reading (walk-by/drive-by/passive drive-by) or fixed network (upgrade without on-site configuration). In combination with Diehl Metering’s IZAR fixed network system, which stands out with extra high coverage and strong performance to reach hard-to-read locations, high data granularity and timeliness will be maintained. This is what makes it a high responsive infrastructure to take actions immediately.

The HYDRUS 2.0 BULK saves daily 512 consumption values. This data can be read locally and accessed only by using the IZAR@MOBILE 2. As a second logging, a small amount of 32 monthly consumption values can be stored. The HYDRUS 2.0 BULK has a minimal sending interval of about 14 seconds and uses the OMS Generation 3 or 4, Profile B security level. Both, the radio protocol and the optical interface are encrypted by default.

  • DN 50 to 200
  • MID approved with dynamic range up to R 1000
  • IP 68 suitable for outdoor installations
  • Integrated radio communication based on Open Metering telegram (OMS Generation 3 or 4, Profile B)
  • Wired M-Bus/Pulse/Pulse, wireless M-Bus, wireless M-Bus in combination with wired L-Bus/Pulse interface
  • Display with error and alarm codes including leakage detection and self-monitoring function
  • Battery lifetime up to 16 years
  • U0 / D0, no need for calming sections
  • General
    Medium temperature range°C+0.1 ... +50
    Ambient operating temperature°C-10 ... +55
    Ambient storage temperature°C-10 ... +70 (>35 °C max. 4 weeks)
    Nominal pressurePNbar16
    Power supply3.6 V lithium battery (D-cell)
    Battery lifetime1Up to 16 years (all communication interfaces)
    Communication interfacesOptical, OMS wireless M-Bus 434 or 868 MHz, M-Bus, L-Bus and Pulse
    Data storageFor errors, alarms and measuring values, data logging capabilities to record up to 512 daily +32 monthly values
    Protection classIP 68
    1 Depends on the sending interval of the radio telegram, the telegram length and the ambient temperature at the installation
  • Technical data display
    Display indicationLCD, 9-digit, additional symbols/display counter/unit
    Units displayed DN 50 - 100Volume (m³ + 2 decimal places) and flow rate (m³/h + 3 decimal places)
    Units displayed DN 125 - 200Volume (m³ + 1 decimal place) and flow rate (m³/h + 3 decimal places)
    Values displayedDisplay test - volume - battery lifetime - firmware version - software checksum - flow - current/continuous/historical error - alarm status - high resolution volume - due date - due date volume - reverse volume - display counter - low battery indication - leakage indication - metrological log access - radio signal ON/OFF - alarm indication - meter lock ON/OFF
  • Interfaces - Overview
    OpticalFor switching the display loop
    Radio434 or 868 MHz, Open Metering Standard radio frame (R3) for mobile reading sent every 14 seconds, long range radio frame (R4) for fixed network sent every 5 minutes, extra long range radio frame (R4+) for fixed network sent every 15 minutes
    M-Bus2400 baud, cable length 1.5 m, power supply only via built-in battery - is combined with two Pulse outputs
    L-BusIn combination with radio, cable length 1.5 m (only one interface communicating at the same time)
    Pulse (Open drain)Two Pulse outputs, or one Pulse and one L-Bus output, Pulse cable length 1.5 m
  • Security
    VersionsOMS Generation 3 or OMS Generation 4, Profile B, selectable
  • Volume / Pulse open drain
    Max. input voltageV30
    Max. input currentmA27
    Max. voltage drop at active outputV/mA2/27
    Max. current through inactive outputμA/V5/30
    Max. reverse voltage without destroying outputsV6 (in case current does not exceed 27 mA)
    Pulse rates DN 50 - 125l/pulse1 / 10 / 100 / 1000
    Pulse rates DN 150l/pulse10 / 100 / 1000
    Pulse rates DN 200l/pulse100 / 1000
    Pulse output 1 variantsTotal volume or forward volume
    Pulse output 2 variantsFlow direction or error, reverse volume
    Pulse frequencyMax. frequency 10 Hz
    Pulse width125 ms
  • Possible communication interfaces
    Wireless M-Bus/Pulse/L-Bus3 wire
    Wireless M-Bus onlywithout wire
    M-Bus/Pulse/Pulse5 wire
    IZAR BE PULSE4 wire
  • Technical Data
    Nominal diameterDNmm506580100125150200
    Permanent flow rateQ3m3/h254063100160250400
    Dynamic (Q3/Q1)R800800800800800800800
    Overload flow rateQ4m³/h31.255078.75125200312.50500
    Transitional flow rateQ2l/h5080126200320500800
    Minimum flow rateQ1l/h31.255078.75125200312.50500
    Starting flow ratel/h1527354570250400
    Pressure loss at Q3bar0.160.150.160.130.150.110.12
    Pressure loss at Q4bar0.250.230.250.20.230.180.19
    Flow rate at ΔP = 1 barm³/h631051582804207471140
  • Approval
    ApprovalMID DE-19-MI001-PTB011
    Dynamic range (Q3/Q1)RUp to 1000
    StandardsISO 4064, EN 14154, OIML R49
    Sanitary conformityKTW/W270, ACS, WRAS
  • Dynamic Range
    Q3 25 ... 400 m³/h - T30R800
    Q3 25 ... 400 m³/h - T50R800H / 250V
  • Dimensions
    Nominal diameterDNmm506580100125150200
    Permanent flow rateQ3m3/h254063100160250400
    Overall lengthLmm200/ 270 / 3002200 / 3002200 / 225 / 300 / 3502250 / 3502 / 360250300 / 500350
    Flange diameterDmm165185200220250285340
    Hole circle diameterKmm125145160180210240295
    Number of screwholespcs44888812
    Screwhole diameterD1mm19191919192323
    HeightHmm748795105120135161
    HeightH1mm121143147165177185215
    HeightH2mm61616161616161
    Counter lengthL1mm98989898989898
    Meter widthBmm165185200220250285340
    Counter widthB1mm139139139139139139139
    Overall weight (approx.)kg7 / 9 / 98 / 1111 / 13 / 14 / 1517 / 19 / 202338 / 4551
    2 Rotatable flange
  • Pressure loss graph / Typical error graph
    Pressure loss graphTypical error graph (DN 100)