SHARKY FS 473

ULTRASONIC FLOW SENSOR

Application

SHARKY FS ultrasonic flow sensor is designed for flow measuring in local and district heating and heating/cooling systems. The ultrasonic technology used is based on the static measurement of the transit time and offers many benefits : no moving parts (prevents wear and tear of the metering components), low pressure loss, large metering dynamics and low start flowrate, resistance to suspended particles...

Features

  • Approval with dynamic range up to 1:250 (qi:qp) MID in class 2 (depending on meter size), standard 1:100
  • Complete range from DN 15 qp 0.6 m³/h up to DN 100 qp 100 m³/h
  • Available in threaded or flanged version
  • Heat-transfer fluid: glycol-free water
  • External power supply as standard or battery-driven as an alternative
  • Low power consumption ensuring optimum battery lifetime (up to 12 years)
  • Applicable for calculators with pulse input
  • Temperature range 5°C to 90°C / 5°C to 150°C
  • General
    ApplicationHeating or bifunctional (heating/cooling) | Heat-transfer fluid: glycol-free water
    ApprovalMID (DE-07-MI004-PTB022)
    Ambient classEN 1434 class C / MID class E2 + M2
    Ambient temperature°C+5 ... +55
    Power supplyExternal power supply: 3.0 ... 5.5 VDC | Battery suply: 3.0 VDC (up to 12 years lifetime)
    Mounting positionAny position
    Protection classHeating: IP 54; heating/cooling: IP 65
    InterfacesOpen Collector pulse output1 - output for testing and communication2
    Volume pulse value310 ml ... 5,000 l/pulse (depending on sensor sizes and supply)
    Pulse cable length2.4 m (4.9 or 9.9 m optional)
    Material of the flow sensor bodyBrass (qp 0.6 ... 10 m³/h), grey cast iron (qp 15 ... 100 m³/h)
    1 The pulse output can be chosen without galvanic isolation (standard) or with galvanic isolation (only with battery supply). The flow sensor has by default a 4-wires pulse cable.
    2 The output for testing is a combined pulse output. The flow sensor can either emit a high resolution test pulse (standard) or communicate via the same output.
    3 The pulse duration is between 1 and 250 ms depending on the pulse value and the nominal flow rate qp.
    Standard pulse values: 1, 10, 100 l/pulse (other pulse values available on request).
  • Temperature range
    Temperature range heating - battery supply°C+5 ...+90 / +5 ... +1051
    Temperature range heating - external supply°C+5 ... +130 / +150
    Temperature range heating/cooling - battery supply°C+5 ... +90 / +5 ... +1051
    1 Only in rising or falling pipes or tilted horizontal installation
  • Technical data
    Nominal flow rateqpm3/h0.61.51.52.5661015254060100
    Nominal diameterDNmm15 15 20 20 25 32 40 50 6580100100
    Overall lengthLmm 110 110 130 130 260 260 300 270 300300360360
    Starting flow ratel/h12.52.54101020405080120120
    Minimum flow rate (DR 1:250)qil/h-661024244016011001160124014001
    Minimum flow rate (DR 1:100)qil/h61515256060100150250400600/1,20021,000/1,2002
    Minimum flow rate (up side down installation)qil/h6661024241001502504001,2001,200
    Maximum flow rateqsm³/h 1.2 3 3 5 12 1220305080120120
    Overload flow ratem³/h 2.5 4.6 4.6 6.7 18.4 18.4 24 36 6090132132
    Pressure loss at qpΔpmbar9512075100128165140140758075210
    Temp. range heating°C5 ... 1305 ... 1305 ... 1305 ... 1305 ... 1505 ... 1505 ... 1505 ... 1505 ... 1505 ... 1505 ... 1505 ... 150
    Kvs value (Δp=Q2/Kvs2)1.954.335.487.9116.7714.7726.7340.0991.29141.42219.09218.22
    1 Valid for horizontal installation only
    2 Up side down installation
  • Dimensions thread version
    Nominal flow rateqpm3/h0.61.51.52.5661015254060100
    Nominal diameterDNmm15 15 20 20 25 32 40 50 6580100100
    Overall lengthLmm 110 110 130 130 260 260 300 270 300300360360
    Overall length with couplingL2mm190190230230380380440-----
    HeightHmm 14.514.51818232333-----
    HeightH1mm 54.554.556.556.5616166.5-----
    Length of electronicL1mm 90909090909090-----
    Width of electronicBmm65.565.565.565.565.565.565.5-----
    Connection thread on meterInchG¾BG¾BG1BG1BG1¼BG1½ BG2B-----
    Connection thread of couplingInchR1R1¼R1½-----
    Operating pressurePNbar16/2516/2516/2516/2516/2516/2516/25-----
    Weightkg0.60.60.610.611.351.352.6-----
  • Dimensions flange version
    Nominal flow rateqpm3/h0.61.51.52.5661015254060100
    Nominal diameterDNmm15 15 20 20 25 32 40 50 6580100100
    Overall lengthLmm 110 110 130 130 260 260 300 270 300300360360
    HeightHmm----5062.56973.58592.5108108
    HeightH1mm----616166.571.57986.596.595.5
    Length of electronicL1mm----9090909090909090
    Width of electronicBmm----65.565.565.565.565.565.565.565.5
    Flange dimensionFmm----100125138147170185216216
    Flange diameterDmm----114139148163184200235235
    Hole circle diameterKmm----85100110125145160190190
    Screwhole diameterD1mm----1418181818192222
    Operating pressurePNbar----16/2516/2516/2516/2516/2516/252525
    Number of screwholespcs----44448888
    Weight brass body1kg----3.354.656.67.459.4511.116.916.9
    Weight grey cast iron body1kg-------6.318.0810.0115.7615.75
    1 Meter with battery and 2.4 m cable length of the pulse cable