SCYLAR INT 8

CALCULATOR
SCYLAR INT 8
heat Thermal Energy » Calculator | Datasheet

Application:

Energy calculator for universal use in systems for heating and cooling measuring. Highly accurate recording of all billing data in local and district heating / cooling systems.


Features:

  • Can be used for heating, cooling or combined heating / cooling
  • Approved according MID
  • Suitable for 2 and 4 wire temperature sensor connection
  • Power save mode
  • NOWA test capability
  • Programmable history memory (daily, weekly, monthly)
  • IZAR@SET parameterization software on Windows basis guarantees optimum adaption to the user specific needs
  • Individual remote reading (AMR) with add on modules Plug & Play
  • Optional with integrated radio, Real Data or Open Metering Standard (868 or 434 MHz)
  • 2 Communication ports (e. g. M-Bus + Radio)
  • Significantly improved radio performance
  • RS485 Interface
  • 2 passive analogue outputs for 4 ... 20mA


General

1: depending on size of flow sensor





SCYLAR INT 8
Application heating - cooling - heating/cooling
Approval MID
Protection class IP 54
Battery supply 3.6 VDC; A cell; 11 years lifetime; 3.6 VDC; D cell; 20 years lifetime
Mains supply 24 VAC; 230 VAC / 0.15W
Volume pulse input frequency max. 200 Hz; pulse durance > 3ms
Pulse value l/pulse 0.01 ... 10,0001
Temperature sensor type Pt 100 or Pt 500 with 2- or 4- wire leads; Ø 5.2 / 6mm
Cable length of temperature sensor Pt 100: 2m; Pt 500: 2/5/10m
Measuring cycle Volume s 2
Measuring cycle Flow s 8

Basic features

1: depending on size of flow sensor





SCYLAR INT 8
Ambient class class E1 + M1
Ambient temperature °C 0 ... 55
Ambient storage temperature °C -25 ... +70
Communication 2 communication slots (e. g. M-Bus + M-Bus; 2 primary adresses, 1 secondary adress)
Integrated Radio Optional
Interfaces standard Optical ZVEI interface
Interfaces optional 2 slots for modules with M-Bus, L-Bus, RS232, RS485, pulse output, pulse input, combined pulse in-/output or analogue output

Integrated Radio

1: depending on size of flow sensor





SCYLAR INT 8
Frequency band 868 or 434 MHz
Type of radio telegram Real Data or Open Metering Standard (OMS)
Transmission data updating Online - no time delay between value measurement and data transmission
Data transmission Unidirectional
Sending interval 12 ... 20 s; depending on length of telegram (duty cycle)

Display

1: depending on size of flow sensor





SCYLAR INT 8
Display indication LCD, 8-digit
Units MWh - kWh - GJ - Gcal - MBtu - gal - GPM - °C - °F - m³
Total values 99,999,999 - 9,999,999.9 - 999,999.99 - 99,999.999
Values displayed Energy - Power - Volume - Flow rate - Temperature and more

Interfaces

1: depending on size of flow sensor





SCYLAR INT 8
Optical ZVEI interface, for communication and testing, M-Bus protocol, 2400 baud
M-Bus Configurable telegram, according to EN1434-3, data reading and parametrization are via two wires with polarity reversal protection, auto baud detect (300 and 2400 baud), 2 M-Bus with 2 primary adresses
RS232 Serial interface for communication with external devices, a special data cable is required, M-Bus protocol, 300 and 2400 baud
RS485 Serial interface for communication with external devices, power supply with 12 V ± 5 V, M-Bus protocol, 2400 baud
Pulse output Module with 2 Open Collector pulse outputs (potential-free), 4 Hz (pulse width 125 ms), 100 Hz (pulse width ≥ 5 ms), ratio: pulse duration / pulse break ~ 1:1, configurable via IZAR@SET software.
Pulse input Module with 2 pulse inputs, max. 20 Hz, configurable via IZAR@SET software, data can be transferred remotely.
Combined pulse in-/output Module with 2 pulse inputs and 1 pulse output, configurable via IZAR@SET software, needed for leak detection.
Analogue output Module for 4 ... 20 mA with 2 programmable passive outputs, programmable value in case of error.

Temperature input

1: depending on size of flow sensor





SCYLAR INT 8
Sensor current mA Pt 100 peak < 8; rms < 0.015, Pt 500 peak < 2; rms < 0.012
Measuring cycle T s with mains unit: 2 s; with A-cell battery: 16 s; with D-cell battery: 4 s
Starting temperature difference ΔΘ K 0.125
Min. temperature difference ΔΘmin K 3
Max. temperature difference ΔΘmax K 177
Absolute temperature measuring range Θ °C -20 ... 190

Dimensions

1: depending on size of flow sensor





SCYLAR INT 8
Overall length L mm 150
Width of calculator B mm 100
Height H mm 54
Back to: CALCULATOR